top of page

Brought to you by Brightspark.blog

Daily Code Question

A daily look at the National Electrical Code

Tuesday December 24th 2024

Todays Daily Code Question.

Q: What is the minimum size for a grounding conductor connected to a ground rod? 

 

Yesterday's Daily Code Question.

Q: What is the primary purpose of grounding and bonding in electrical systems?

A:  The purpose is to provide a path for fault current to safely return to the source in order to, 
•    Prevent electrical shock
•    Minimize the risk of fire or equipment damage 

Monday December 23rd 2024

Todays Daily Code Question.

Q: What is the primary purpose of grounding and bonding in electrical systems?

 

Friday's Daily Code Question.

Q: How is the feeder load for a hotel or motel guest room calculated? 

A:  Guest rooms in hotels and motels are calculated at 1,800 VA per room for general lighting and receptacle loads. Additional loads like HVAC or appliances are added separately. Reference 220.12(B) 

Friday December 20th 2024

Todays Daily Code Question.

Q: How is the feeder load for a hotel of motel guest room calculated? 

 

Yesterday's Daily Code Question.

Q: What is the demand factor for marinas and boatyards? 

A:  Per NEC 220.44 demand factors for marinas are not directly listed in Article 220. Loads are calculated per actual connected devices and adjusted according to Article 555 requirements. 

Thursday December 19th 2024

Todays Daily Code Question.

Q: What is the demand factor for marinas and boatyards? 

 

Yesterday's Daily Code Question.

Q: How is a combination of heating and cooling loads accounted for in a dwelling? 

A:  Per NEC 220.60 calculate only for the larger of the two loads 

Wednesday December 18th 2024

Todays Daily Code Question.

Q: How is a combination of heating and cooling loads accounted for in a dwelling? 

 

Yesterday's Daily Code Question.

Q: What is the load calculation for receptacles in industrial buildings? 

A:  Per NEC 220.14(I) the load is calculated as 180VA per single or multiple receptacle outlet. For larger systems demand factors from 220.42 may apply. 

Tuesday December 17th 2024

Todays Daily Code Question.

Q: What is the load calculation for receptacles in industrial buildings? 

 

Yesterday's Daily Code Question.

Q:  How is an appliance load calculated when it is not explicitly listed in the NEC?

A:  Per NEC 220.14(A) the connected load of the appliance based on its nameplate rating must be included in the calculation. For continuous appliances multiply by 125% 

Monday December 16th 2024

Todays Daily Code Question.

Q: How is an appliance load calculated when it is not explicitly listed in the NEC?

 

Friday's Daily Code Question.

Q:  What is the minimum service size for a single-family dwelling? 

A: The minimum service size for a single-family dwelling is 100 amperes ( per NEC 230.(79) but load calculations per Article 220 determine the actual required service size. 

Friday December 13th 2024

Todays Daily Code Question.

Q: What is the minimum service size for a single-family dwelling? 

 

Yesterday's Daily Code Question.

Q:  How do you calculate the load for data processing equipment?

A: For feeder and branch circuits supplying information technology equipment, calculate per NEC 220.14(H). Add 120 VA per receptacle and follow specific equipment ratings.

Thursday December 12th 2024

Todays Daily Code Question.

Q: How do you calculate the load for data processing equipment?

 

Yesterday's Daily Code Question.

Q:  How is the load calculated for show window lighting?

A: Per NEC 220 14(G) calculate 200VA per linear foot of the show window. This ensures adequate power supply for the lighting system. 

Wednesday December 11th 2024

Todays Daily Code Question.

Q: How is the load calculated for show window lighting?

 

Yesterday's Daily Code Question.

Q:  What are the requirements for calculating feeder and service loads in schools?

A: For schools equipped with electric space heating air conditioning or both, the calculation of a feeder or service load is permitted in accordance with table 220.86 This table provides demand factors based on the connected load per square foot.

Tuesday December 10th 2024

Todays Daily Code Question.

Q: What are the requirements for calculating feeder and service loads in schools?

 

Yesterday's Daily Code Question.

Q:  What is the purpose of applying demand factors in load calculations?

A: Demand factors account for the likelihood that not all electrical loads will operate simultaneously at their maximum capacity. Applying these factors results in more realistic and often lower load calculations, leading to appropriately sized electrical systems that are both safe and cost-effective.

Monday December 9th 2024

Todays Daily Code Question.

Q: What is the purpose of applying demand factors in load calculations?

 

Friday's Daily Code Question.

Q:  Are spare circuits included in load calculations?

A: Yes, per 220.14(J) Spare or unused circuits must be included in load calculations at 180VA per outlet or device. 

Friday December 6th 2024

Todays Daily Code Question.

Q: Are spare circuits included in load calculations?

 

Yesterday's Daily Code Question.

Q:  What is the demand factor for track lighting loads?

A: Per 220.43(B) for track lighting other than in dwelling units the load must be calculated at 150 VA per linear foot of track 

Thursday December 5th 2024

Todays Daily Code Question.

Q: What is the demand factor for track lighting loads?

 

Yesterday's Daily Code Question.

Q:  What is the load calculation required for electric clothes dryers in dwelling units? 

A: NEC 220.54 requires a minimum load of 5,000 VA or the nameplate of the dryer, whichever is larger. Demand factors from table 220.54 can be applied when multiple dryers are used.

Wednesday December 4th 2024

Todays Daily Code Question.

Q: What is the load calculation required for electric clothes dryers in dwelling units? 

 

Yesterday's Daily Code Question.

Q:  When calculating loads, how is a continuous load defined?

A: A continuous load is one that operates for three hours or more at its maximum current. Article 220 requires continuous loads to be calculated at 125% of their rated load to ensure safe operation.

Tuesday December 3rd 2024

Todays Daily Code Question.

Q: When calculating loads, how is a continuous load defined?

 

Yesterday's Daily Code Question.

Q:  How are motor loads considered in load calculations?

A: NEC 220.50 requires that motor loads be calculated based on the motors full load current, with adjustments for continuous operation and other applicable factors. The calculated load includes the motors highest starting current and all other connected loads.

Monday December 2nd 2024

Todays Daily Code Question.

Q: How are motor loads considered in load calculations?

 

Friday's Daily Code Question.

Q:  What is the significance of Table 220.42 in NEC article 220?

A: Table 220.42 provides demand factors for general lighting in non-dwelling occupancies, (like hotels and stores). It allows a reduced calculated load based on occupancy type, helping to size circuits and feeders appropriately. 

Friday November 29th 2024

Todays Daily Code Question.

Q: What is the significance of Table 220.42 in NEC article 220?

 

Wednesday's Daily Code Question.

Q:  How are load calculations for fixed electric space heating equipment conducted?

A: For fixed electric space heating, NEC 220.51 requires calculating the load at 100% of the equipment’s rated load, as these loads are continuous and must be considered fully in load calculations. 

Wednesday November 27th 2024

Todays Daily Code Question.

Q: How are load calculations for fixed electric space heating equipment conducted?

 

Tuesday's Daily Code Question.

Q:  What are the optional methods in NEC article 220, and when can they be used?

A: Optional methods are alternative calculation methods provided in NEC 220, part IV, which can be used for dwelling units, multifamily dwellings, and specific building types to simplify load calculations under certain conditions. Optional Methods can be used when they are specifically permitted by the NEC and applicable to the building type. 
​When the optional method simplifies the calculation without compromising safety. 
​When demand factors or historical data provide a more accurate load calculation than the standard method. 
​When using these methods can save costs on service and feeder sizing, as well as ensuring that the electrical installation is appropriate for actual load demands. 

Tuesday November 26th 2024

Todays Daily Code Question.

Q: What are the “Optional" Calculation Methods for single-family dwellings, and why are they useful?

 

Yesterday's Daily Code Question.

Q:  How do you determine the load for commercial kitchen equipment?

A: NEC 220.56 provides demand factors for commercial kitchen equipment, allowing a reduced calculated load based on the number of units. This is particularly useful for restaurants and facilities with multiple appliances. Steps to be taken are,

1. Identify the equipment and nameplate ratings. 

2. Apply demand factors, 100% for the first 14kVA, 65% for any amount over 14 kVA.

3. Include other equipment loads.

4. Include non-cooking loads. 

5. Ensure proper voltage and phase are considered for the equipment. 

6. For any equipment classified as a continuous load multiply the calculated load by 125%

Monday November 25th 2024

Todays Daily Code Question.

Q: How do you determine the load for commercial kitchen equipment?

Friday's Daily Code Question.

Q:  What is the load calculation required for electric clothes dryers in dwelling units? 

A: NEC 220.54 requires a minimum load of 5,000 VA or the nameplate of the dryer, whichever is larger. Demand factors from table 220.54 can be applied when multiple dryers are used.

Friday November 22th 2024

Todays Daily Code Question.

Q: What is the load calculation required for electric clothes dryers in dwelling units? 

Yesterday's Daily Code Question.

Q:  When calculating loads, how is a continuous load defined?

A: A continuous load is one that operates for three hours or more at its maximum current. Article 220 requires continuous loads to be calculated at 125% of their rated load to ensure safe operation.
 

Thursday November 21th 2024

Todays Daily Code Question.

Q: When calculating loads, how is a continuous load defined?

Yesterday's Daily Code Question.

Q:  How are motor loads considered in load calculations?

A: NEC 220.50 requires that motor loads be calculated based on the motors full load current, with adjustments for continuous operation and other applicable factors. The calculated load includes the motors highest starting current and all other connected loads.
 

Wednesday November 20th 2024

Todays Daily Code Question.

Q: How are motor loads considered in load calculations?

Yesterday's Daily Code Question.

Q:  What is the significance of Table 220.42 in NEC article 220?

A: Table 220.42 provides demand factors for general lighting in non-dwelling occupancies, (like hotels and stores). It allows a reduced calculated load based on occupancy type, helping to size circuits and feeders appropriately. 

Tuesday November 19th 2024

Todays Daily Code Question.

Q: What is the significance of Table 220.42 in NEC article 220?

Yesterday's Daily Code Question.

Q:  How are load calculations for fixed electric space heating equipment conducted?

A: For fixed electric space heating, NEC 220.51 requires calculating the load at 100% of the equipment’s rated load, as these loads are continuous and must be considered fully in load calculations. 

Monday November 18th 2024

Todays Daily Code Question.

Q: How are load calculations for fixed electric space heating equipment conducted?

Friday's Daily Code Question.

Q:  What are the optional methods in NEC article 220, and when can they be used?

A: Optional methods are alternative calculation methods provided in NEC 220, part IV, which can be used for dwelling units, multifamily dwellings, and specific building types to simplify load calculations under certain conditions. 

Optional Methods can be used when they are specifically permitted by the NEC and applicable to the building type. 

When the optional method simplifies the calculation without compromising safety. 

When demand factors or historical data provide a more accurate load calculation than the standard method. 

When using these methods can save costs on service and feeder sizing, as well as ensuring that the electrical installation is appropriate for actual load demands. 

Thursday November 14th 2024

Todays Daily Code Question.

Q:  When calculating loads, how is a continuous load defined?

 

Yesterday's Daily Code Question.

Q: How are motor loads considered in load calculations?

A: NEC 220.50 requires that motor loads be calculated based on the motors full load current, with adjustments for continuous operation and other applicable factors. The calculated load includes the motors highest starting current and all other connected loads.

Wednesday November 13th 2024

Todays Daily Code Question.

Q:  What is the neutral load and how is it determined? 

 

Yesterday's Daily Code Question.

Q: What are the steps to calculate a service load for a dwelling unit? 

A: Some of the key steps are,
•  Calculate the lighting load based on square footage,
•  Add small appliance and laundry load,
•  Include fixed appliance loads like water heaters or dryers,
•  Apply demand factors where allowed for a reduced total load.

Tuesday November 12th 2024

Todays Daily Code Question.

Q:  What are the steps to calculate a service load for a dwelling unit? 

 

Yesterday's Daily Code Question.

Q: How is the load for electric ranges calculated in NEC article 220?

A: The load for electric ranges is calculated using NEC table 220.55 which provides demand factors based on the number and size of ranges to avoid oversizing.

Monday November 11th 2024

Todays Daily Code Question.

Q:  How is the load for electric ranges calculated in NEC article 220?

 

Friday's Daily Code Question.

Q: What is the minimum load calculation requirement for laundry circuits in a dwelling unit?  

A: NEC 220.52(B) requires a minimum load of 1,500 VA for a dedicated laundry circuit in a dwelling unit. 

Friday November 8th 2024

Todays Daily Code Question.

Q: What is the minimum load calculation requirement for laundry circuits in a dwelling unit?   

 

Yesterday's Daily Code Question.

Q: How are small appliance loads accounted for in dwelling units and what article of the NEC addresses this topic?

A: NEC 220.52 requires at least two small-appliance branch circuits for kitchens, each calculated at 1500VA. These loads must be included in the dwelling unit load calculation.

Thursday November 7th 2024

Todays Daily Code Question.

Q: How are small appliance loads accounted for in dwelling units and what article of the NEC addresses this topic?

 

Yesterday's Daily Code Question.

Q: What is the demand factor and why is it important in load calculations?

A: A demand factor allows reduced load calculations based on the assumption that not all electrical equipment will operate simultaneously. Article 220 uses demand factor to prevent oversizing electrical systems. 

Wednesday November 6th 2024

Todays Daily Code Question.

Q: What is the demand factor and why is it important in load calculations?

 

Yesterday's Daily Code Question.

Q: How is the general lighting load calculated for a dwelling unit?

A: For dwelling units the general lighting load is calculated at 3VA per square foot as per NEC 220.12

Tuesday November 5th 2024

Todays Daily Code Question.

Q: How is the general lighting load calculated for a dwelling unit?

 

Yesterday's Daily Code Question.

Q: What is the main focus of NEC Article 220? 

A: NEC Article 220 provides guidelines for calculating branch-circuit, Feeder, and service loads to ensure electrical systems are safely and adequately sized. 

Monday November 4th 2024

Todays Daily Code Question.

Q: What is the main focus of NEC Article 220? 

 

Friday's Daily Code Question.

Q: Although not a mandatory rule, NEC 215.2(A)(4) recommends a maximum voltage drop percentage for feeders. What is the recommended maximum and why is it suggested?

A: The NEC recommends a maximum voltage drop of 3% for feeders to maintain efficiency and avoid excess energy loss. This helps ensure that the connected equipment receives sufficient voltage for reliable operation.

Friday November 1st 2024

Todays Daily Code Question.

Q: Although not a mandatory rule, NEC 215.2(A)(4) recommends a maximum voltage drop percentage for feeders. What is the recommended maximum and why is it suggested?

 

Yesterday's Daily Code Question.

Q: When sizing conductors according to NEC 215.2(A)(1), what additional considerations might require adjusting the conductor size beyond the minimum calculated load.

A: Feeder conductor sizing may require adjustments for factors like ambient temperature, conductor bundling, voltage drop, or correction factors for specific environmental conditions as outlined in NEC Article 310. 

Thursday October 31st 2024

Todays Daily Code Question.

Q: When sizing conductors according to NEC 215.2(A)(1), what additional considerations might require adjusting the conductor size beyond the minimum calculated load.

 

Yesterday's Daily Code Question.

Q: NEC 215.10 outlines requirements for feeders in hazardous locations, What are some of the protective measures required for feeders installed in these areas?

A: Feeders in hazardous locations must be protected in ways that prevent ignition of the surrounding atmosphere. This may include using explosion-proof enclosures, installing sealed conduit fittings and selecting conductors and protective devices rated for the specific class and division of the hazardous location.
 

Wednesday October 30th 2024

Todays Daily Code Question.

Q: NEC 215.10 outlines requirements for feeders in hazardous locations, What are some of the protective measures required for feeders installed in these areas?

 

Yesterday's Daily Code Question.

Q:  What is the minimum ampacity required for a feeder conductor?

A: Refer to NEC 215.(A)(1) and the calculation methods outlined in NEC 310.15 to determine the correct conductor size based on the connected load. 

Tuesday October 29th 2024

Todays Daily Code Question.

Q: What is the minimum ampacity required for a feeder conductor?

 

Yesterday's Daily Code Question.

Q:  What is the rule for feeder conductor sizing when supplying continuous loads.

A: According to NEC 215.2(A)(1) (a) feeder conductors must be sized to carry not less than 125% of the continuous load.

Monday October 28th 2024

Todays Daily Code Question.

Q: What is the rule for feeder conductor sizing when supplying continuous loads.

 

Friday's Daily Code Question.

Q:  What factors must be considered when determining the overcurrent protection for a feeder circuit? 

A: NEC 215.3 requires that the feeders overcurrent protection device (OCPD) must be sized based on their ampacity and the connected load, including the adjustments for continuous loads.

Friday October 25th 2024

Todays Daily Code Question.

Q:  What factors must be considered when determining the overcurrent protection for a feeder circuit? 

 

Yesterday's Daily Code Question.

Q: In what situations can feeder neutral conductors be smaller than the ungrounded conductors? 

A: NEC 215.2 provides conditions under which the neutral can be reduced, such as when the neutral load is less than the phase load. In addition, in a balanced three-phase system the currents in the three phase conductors effectively cancel each other out resulting in minimal or no current on the neutral.

Thursday October 24th 2024

Todays Daily Code Question.

Q:  In what situations can feeder neutral conductors be smaller than the ungrounded conductors? 

 

Yesterday's Daily Code Question.

Q:  What is the importance of NEC 215.15 for arc-fault protection? 

A: Although NEC 215.15 deals specifically with ground-fault protection for large feeder systems, protecting against ground faults can help prevent the conditions that may lead to arc-faults. Ground faults if not interrupted can lead to overheating of conductors or equipment leading to an increased chance of arcing.

Uninterrupted ground faults can deteriorate insulation which could also lead to arcing faults. By mandating ground-fault protection in large systems NEC 215.15 indirectly helps prevent potential fires or equipment damage including those that could evolve into arc-faults.

Wednesday October 23nd 2024

Todays Daily Code Question.

Q:  What is the importance of NEC 215.15 for arc-fault protection? 

 

Yesterday's Daily Code Question.

Q:  Does NEC article 215 require feeders to be grounded? 

A:  Yes, NEC 215.6 requires grounding for all feeder circuits. Feeders should have an effective grounding path to ensure that any fault currents are safely diverted back to ground preventing shock hazards and equipment damage. 

Tuesday October 22nd 2024

Todays Daily Code Question.

Q:  Does NEC article 215 require feeders to be grounded? 

 

Yesterday's Daily Code Question.

Q:  What are the labeling requirements for feeder circuits under NEC article 215? 

A:  NEC 215.12 requires that feeder circuits be labelled to identify them clearly, especially in installations where multiple feeders are present. This helps ensure safety and simplifies maintenance and troubleshooting. 

Monday October 21st 2024

Todays Daily Code Question.

Q:  What are the labeling requirements for feeder circuits under NEC article 215? 

 

Friday's Daily Code Question.

Q:  Are feeder tap conductors permitted under NEC article 215, and if so under what conditions? 

A: Yes feeder tap conductors are permitted as outlined in NEC 215.2(A)(2) and article 240.21(B). They must sized appropriately and be limited in length to reduce the risk of overcurrent protection issues, such as ensuring adequate protection and avoiding excessive conductor length without additional protection. 

Friday October 18th 2024

Todays Daily Code Question.

Q:  Are feeder tap conductors permitted under NEC article 215, and if so under what conditions? 

 

Yesterday's Daily Code Question.

Q:  What does the NEC say about feeders supplying multiple buildings or structures? 

A: NEC 215.4 requires that feeders supplying multiple buildings or structures on the same property should be designed to handle the total load and have separate overcurrent protection for each building or structure. 

Thursday October 17th 2024

Todays Daily Code Question.

Q:  What does the NEC say about feeders supplying multiple buildings or structures? 

 

Yesterday's Daily Code Question.

Q:  Are there any specific NEC requirements regarding conductor ampacity adjustments for temperature or environmental conditions?

A: Yes, NEC 215.2(A)(3) specifies that conductor ampacity may need adjustments based on ambient temperature, the number of current-carrying conductors and other environmental factors. These adjustments ensure the conductor remains within safe temperature limits. 

Wednesday October 16th 2024

Todays Daily Code Question.

Q: Are there any specific NEC requirements regarding conductor ampacity adjustments for temperature or environmental conditions? 

 

Yesterday's Daily Code Question.

Q:  Can feeders serve multiple loads, and what factors should be considered? 

A: Yes feeders can serve multiple loads, however NEC 215.2 and 220 require calculations of both continuous loads and non-continuous loads to size feeders properly. Also considerations for diversity factors and load balancing should be accounted for. 

Tuesday October 15th 2024

Todays Daily Code Question.

Q: Can feeders serve multiple loads, and what factors should be considered? 

 

Yesterday's Daily Code Question.

Q:  What does NEC article 215.3 specify about feeder conductor overcurrent protection? 

A: Per NEC 215.3 feeders must be protected by an overcurrent device at the point where they receive their supply, sized to protect the conductors ampacity. The device should be rated to prevent overloading and should trip if there is an excess current flow.

Monday October 14th 2024

Todays Daily Code Question.

Q: What does NEC article 215.3 specify about feeder conductor overcurrent protection? 

 

Friday's Daily Code Question.

Q:  What is required by NEC 215.10 regarding ground fault protection?

A: NEC 215.10 mandates that feeders supplying equipment requiring ground fault protection for personnel must have ground fault protection installed. This requirement is generally for feeders over 1000 amps and systems of 480 Volts or more

Friday October 11th 2024

Todays Daily Code Question.

Q: What is required by NEC 215.10 regarding ground fault protection?

 

Yesterday's Daily Code Question.

Q:  When sizing feeder conductors what factors must be considered according to NEC 215.2?

A: According to the NEC 215.2 feeder conductor sizing must consider the ampacity needed to handle the load, any applicable temperature corrections and demand factors. Conductors must also be sized to carry the load current continuously and account for voltage drop when needed. 

Thursday October 10th 2024

Todays Daily Code Question.

Q: When sizing feeder conductors what factors must be considered according to NEC 215.2?

 

Yesterday's Daily Code Question.

Q:  What does 215.2(A)(1) recommend regarding voltage drop for feeder circuits? 

A: Although not a requirement, Article 215.2(A)(1) recommends that feeder conductors be sized to limit the voltage drop to 3% for feeder circuits and 5% for the combined voltage drop of feeders and branch circuits to ensure efficient operation of electrical equipment.

Wednesday October 9th 2024

Todays Daily Code Question.

Q: What does 215.2 (A)(1) recommend regarding voltage drop for feeder circuits? 

 

Yesterday's Daily Code Question.

Q:  How is the minimum feeder neutral load calculated as per Article 215.5?

A: The minimum feeder neutral load must be calculated based on the maximum unbalanced load between the neutral and any one ungrounded conductor. This calculation follows the methods described in article 220 which covers load calculations for feeders and branch circuits. 

Tuesday October 8th 2024

Todays Daily Code Question.

Q: How is the minimum feeder neutral load calculated as per Article 215.5?

 

Yesterday's Daily Code Question.

Q:  What is the maximum length for a feeder tap conductor as described in Article 215.2 and under what conditions can this limit be exceeded? 

A: Feeder taps must comply with the requirements set forth in Article 240.21(B). For example a tap conductor up to 10 feet in length may be used if it meets specific conditions regarding the ampacity and physical protection of the conductor. Taps longer than 10 feet but up to 25 feet are allowed if the conditions set forth for 25 foot tap rules are met, including protection from damage and ensuring that the feeder tap is terminated in an appropriate overcurrent protective device. 

Monday October 7th 2024

Todays Daily Code Question.

Q:What is the maximum length for a feeder tap conductor as described in Article 215.2 and under what conditions can this limit be exceeded? 

 

Friday's Daily Code Question.

Q:   What special rules apply to feeders that supply power to multiple buildings or structures? 

A: Feeders supplying power to multiple buildings or structures must have disconnecting means that are readily accessible at each building or structure and must also comply with the requirements of article 225 which deals with outside branch circuits and feeders.

Friday October 4th 2024

Todays Daily Code Question.

Q: What special rules apply to feeders that supply power to multiple buildings or structures? 

 

Yesterday's Daily Code Question.

Q:   How does the NEC define the requirements for feeder overcurrent protection? 

A: Article 215.3 requires that feeders be protected against overcurrent in accordance with their ampacity. Overcurrent protection must not exceed the ampacity of the conductors and must be installed at the point where the conductors receive their supply. 

Thursday October 3rd 2024

Todays Daily Code Question.

Q: How does the NEC define the requirements for feeder overcurrent protection? 

 

Yesterday's Daily Code Question.

Q:  How is the minimum ampacity of feeder conductors determined?

A: The minimum ampacity of feeder conductors is determined by the sum of the loads on the circuits supplied by the feeder as specified in Article 220 and must be based on the loads served. The ampacity must also account for continuous loads which must be 125% of the continuous loads. 

Wednesday October 2nd 2024

Todays Daily Code Question.

Q: How is the minimum ampacity of feeder conductors determined?

 

Yesterday's Daily Code Question.

Q:  What is the definition of a feeder in article 215 of the NEC? 

A: A feeder is all circuit conductors between the service equipment, the source of a separately derived system or other power supply source and the final branch circuit overcurrent device. 

Tuesday October 1st 2024

Todays Daily Code Question.

Q: What is the definition of a feeder in article 215 of the NEC? 

 

Yesterday's Daily Code Question.

Q:  The NEC addresses the sizing of branch circuit conductors, what must the ampacity of these conductors be based on? 

A:

1. The load to be served, 210.19(A). The ampacity of branch circuit conductors must be based on the maximum load that will be served by the circuit. Additionally branch circuit conductors must have an ampacity not less than the rating of the undercurrent protection device that is protecting the circuit, except as modified for motor circuits and other specific cases outlined in the NEC.  

2. Continuous vs Non-continuous loads, ( loads to run for 3 hours or more. 

Conductors to be sized at 125% of the continuous load.

3. Conductor temperature rating as per table 310.16.

4. Ambient temperature Adjustments as per table 310.15(B)(1)

Number of conductors in a conduit, as per table 310.15(B)(3)(a)

Monday September 30th 2024

Todays Daily Code Question.

Q: The NEC addresses the sizing of branch circuit conductors, what must the ampacity of these conductors be based on? 

 

Friday's Daily Code Question.

Q:  What is the required number of receptacles in a bedroom as per NEC requirements?

A: Receptacles must be placed so that no point along the floor line in any wall space is more than 6 feet from a receptacle. This means that for every wall in the bedroom receptacles must be spaced such that no part of the wall is more than 6 feet from an outlet, meaning that there must be a receptacle every 12 feet along the wall line. 210.52(A)

Friday September 27th 2024

Todays Daily Code Question.

Q:  What is the required number of receptacles in a bedroom as per the NEC. 

Yesterday's Daily Code Question.

Q: According to the NEC how must lighting outlets be installed in attics, underfloor spaces, utility rooms, and basements?

A: At least one lighting outlet containing a switch or controlled by a wall switch must be installed at the point of entry, in attics, underfloor spaces, utility rooms, crawl spaces and basements where these spaces are used for storage or contain equipment that require servicing. The lighting outlet must be installed near the equipment to provide adequate lighting for service personnel. In basements at least one lighting outlet is required controlled by a wall switch. 

Thursday September 26th 2024

Todays Daily Code Question.

Q:  According to the NEC how must lighting outlets be installed in attics, underfloor spaces, utility rooms, and basements?

Yesterday's Daily Code Question.

Q: What is the maximum number of receptacle outlets allowed on a single 20 amp branch circuit in a commercial occupancy according to NEC guidelines? 

A: Although the NEC does not explicitly state a maximum number of receptacles for a 20 amp circuit, it is a common practice to apply the general rule of 180 volt amperes per receptacle when designing commercial circuits. This means that a typical 20 amp 120 volt circuit could theoretically supply up to 13 receptacle outlets. 20A X 120V = 2400VA divided by 180VA = 13.3 outlets. NEC 220.14(I)

Wednesday September 25th 2024

Todays Daily Code Question.

Q:  What is the maximum number of receptacle outlets allowed on a single 20 amp branch circuit in a commercial occupancy according to NEC guidelines? 

Yesterday's Daily Code Question.

Q: Can a single 20 amp branch circuit supply both a kitchen refrigerator and general lighting?

A: No, As per NEC 210.23(A)(2) the 20 amp branch circuit can supply appliances and equipment but must not exceed 80% of the circuit’s rating if supplying multiple outlets including lighting. It is common practice to provide dedicated circuits for appliances like refrigerators. 

Tuesday September 24th 2024

Todays Daily Code Question.

Q: Can a single 20 amp branch circuit supply both a kitchen refrigerator and general lighting? 

Yesterday's Daily Code Question.

Q: Is a receptacle outlet required in a walk-in closet? 

A: NEC 210.52 does not require receptacle outlets in closets, however if lighting is installed it must comply with NEC 410 regarding clearances and safe placement of fixtures in closets.

Monday September 23rd 2024

Todays Daily Code Question.

Q: Is a receptacle outlet required in a walk-in closet? 

Friday's Daily Code Question.

Q: What are the NEC requirements for receptacle outlets in an unfinished basement as stated in NEC 210.52(G)(3) ?

A: At least one receptacle outlet must be installed in an unfinished basement and GFCI  protection is required for all 120V single phase 15 and 20 amp receptacles in unfinished areas of basements. 

Friday September 20th 2024

Todays Daily Code Question.

Q: What are the NEC requirements for receptacle outlets in an unfinished basement as stated in NEC 210.52(G)(3) ?

Yesterday's Daily Code Question.

Q:  NEC 210.19(A)(1) addresses branch circuit conductor sizing for continuous loads, How must branch circuits supplying lighting loads be sized? 

A: Branch circuits supplying lighting loads that are continuous (operating for 3 hours or more) must be sized at 125% of the continuous load to avoid overheating of conductors. 

Thursday September 19th 2024

Todays Daily Code Question.

Q: NEC 210.19(A)(1) addresses branch circuit conductor sizing for continuous loads, How must branch circuits supplying lighting loads be sized? 

Yesterday's Daily Code Question.

Q:  What special provision is required for multi-wire branch circuits as per NEC 210.4(B) 

A: Multi-wire branch circuits must have a means to simultaneously disconnect all ungrounded hot conductors at the point where the branch circuit originates This ensures that all legs of the multi-wire branch circuit are de-energized when working on a circuit. 

Wednesday September 18th 2024

Todays Daily Code Question.

Q: What special provision is required for multi-wire branch circuits as per NEC 210.4(B) 

Yesterday's Daily Code Question.

Q:  What are the requirements for electrical outlets in in attached and detached garage spaces with electrical power? 

A: One 15A or 20A receptacle outlet is required in each attached or detached garage with electrical power. The branch circuit supplying this receptacle must not supply outlets outside the garage. At least one outlet must be provided for each car space. 210.52(G)(1) 

Tuesday September 17th 2024

Todays Daily Code Question.

Q: What are the requirements for electrical outlets in in attached and detached garage spaces with electrical power?

Yesterday's Daily Code Question.

Q:  What are the receptacle location requirements for kitchen countertop outlets? 

A: Countertop receptacle outlets must be located on or above, but not more than 20 inches above the kitchen countertop.210.52(C)(5)

Monday September 16th 2024

Todays Daily Code Question.

Q: What are the receptacle location requirements for kitchen countertop outlets? 

Friday's Daily Code Question.

Q:  In what circumstances are kitchen countertop spaces considered separate countertops as it pertains to outlet placement? 

A: When breaks occur in countertop spaces for range-tops, refrigerators, or sinks, each countertop is considered as a separate countertop. 210.52(C)(4)

Friday September 13th 2024

Todays Daily Code Question.

Q: In what circumstances are kitchen countertop spaces considered separate countertops as it pertains to outlet placement? 

Yesterday's Daily Code Question.

Q:  What is the definition of a wall space as it pertains to outlet spacing as per NEC guidelines? 

A: A wall space is any wall 2 feet or more in width, unbroken along the floor line by doorways or similar openings, fireplaces, or fixed cabinets. 210.52(A)(2)(1)

Thursday September 12th 2024

Todays Daily Code Question.

Q: What is the definition of a wall space as it pertains to outlet spacing as per NEC guidelines? 

Yesterday's Daily Code Question.

Q:  What are the lighting outlet requirements for stairways in a dwelling unit? 

A: NEC 210.70(A)(2) requires that stairways must have a lighting outlet controlled by a wall switch at each level where the stairs have 6 or more risers. This ensures adequate lighting and safety when moving up or down stairs. 

Wednesday September 11th 2024

Todays Daily Code Question.

Q:What are the lighting outlet requirements for stairways in a dwelling unit? 

Yesterday's Daily Code Question.

Q:  According to the NEC how many receptacles are required in the bathroom of a dwelling unit? 

A: According to the NEC at least one GFCI protected outlet is required in every bathroom located within 3 feet of the outside edge of the sink. This is intended to provide convenient access to electricity while reducing the risk of electric shock. NEC210.52(D)

Tuesday September 10th 2024

Todays Daily Code Question.

Q: According to the NEC how many receptacles are required in the bathroom of a dwelling unit? 

Yesterday's Daily Code Question.

Q: What is the maximum allowable voltage drop for branch circuits and feeders according to NEC guidelines?

A: The NEC recommends that the voltage drop for branch circuits should not exceed 3% at the furthest outlet and the total voltage drop for feeders and branch circuits should not exceed 5% to ensure proper operation of electrical equipment. NEC 210.19(A) NEC215.2(A)

Monday September 9th 2024

Todays Daily Code Question.

Q: What is the maximum allowable voltage drop for branch circuits and feeders according to NEC guidelines?

Friday's Daily Code Question.

Q: Which areas of a dwelling unit require AFCI protection for branch circuits supplying 120v single phase 15 and 20 amp outlets? 

A: AFCI protection is required in Kitchens, Family rooms, Dining rooms, Living-rooms, Parlors, Libraries, Dens, Bedrooms, Sunrooms, Recreation rooms, Closets, Hallways, Laundry areas and any similar areas. NEC 210.12(A)

Friday September 6th 2024

Todays Daily Code Question.

Q: Which areas of a dwelling unit require AFCI protection for branch circuits supplying 120v single phase 15 and 20 amp outlets? 

Yesterday's question.

Q:  Where are receptacles required in outdoor areas of a dwelling unit and what specific protection is needed? 

A: At least one receptacle outlet is required in the front and back of a dwelling unit. These outdoor receptacles must have GFCI protection and must be installed in a weatherproof enclosure that remains weatherproof with the attachment plug cap inserted. NEC 406.9(B)(1)

Thursday September 5th 2024

Todays Daily Code Question.

Q: Where are receptacles required in outdoor areas of a dwelling unit and what specific protection is needed? 

Yesterday's question.

Q:  What are the requirements for disconnecting means for a multi-wire branch circuit? 

A: NEC 210.4 requires that a multi-wire branch circuit must have a means to simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates. 
This is typically done with a double pole circuit breaker or two single pole breakers with a handle tie. 

Wednesday September 4th 2024

Todays Daily Code Question.

Q: What are the requirements for disconnecting means for a multi-wire branch circuit? 

Yesterday's question.

Q:  What special provisions are made for branch circuits in guest rooms and guest suites of hotels and motels? 

A: 210.60. Branch circuits in guest rooms and guest suites must be arranged to provide adequate power for general-purpose receptacles, lighting, and any other specific loads like air conditioning or heating. The circuits should be designed to handle the anticipated loads. 

Tuesday September 3rd 2024

Todays Daily Code Question.

Q: What special provisions are made for branch circuits in guest rooms and guest suites of hotels and motels? 

Friday's question.

Q: What are the NEC requirements with regard to receptacle outlets in relation to heating, air-conditioning, and refrigeration equipment?

A: A receptacle outlet must be installed within 25 feet of the heating, air-conditioning, and refrigeration equipment as per NEC 210.63

Friday August 30th 2024

Todays Daily Code Question.

Q: What are the NEC requirements with regard to receptacle outlets in relation to heating, air-conditioning, and refrigeration equipment?

Yesterday's question.

Q: What are the NEC requirements for receptacle outlets in basements and garages? 

A: NEC 210.52(G) At least one receptacle outlet must be installed in each unfinished basement and in each attached garage. Additionally for each detached garage or accessory building with electrical power at least one receptacle outlet must be installed. 

Thursday August 29th 2024

Todays Daily Code Question.

Q: What are the NEC requirements for receptacle outlets in basements and garages? 

Yesterday's question.

Q: What are the NEC requirement for receptacles in hallways? 

A. : NEC 210.52(H) Hallways that are 10 feet or longer must have at least one receptacle outlet. 

The length of the hallway is measured along the centerline without passing through a doorway. 

Wednesday August 28th 2024

Todays Daily Code Question.

What is the NEC requirement for receptacles in hallways? 
 

Yesterday's question.

Q: What size branch circuit is required for a bathroom receptacle in a dwelling unit? 

A. NEC 210.11(C)(3). At least one 20-amp branch circuit is required to supply the bathroom receptacle outlets. This circuit must not supply any other outlets or lighting outside the bathroom. 

Tuesday August 27th 2024

Todays Daily Code Question.

What size branch circuit is required for a bathroom receptacle in a dwelling unit? 
 

Yesterday's question.

Q: What is the minimum size branch circuit (in amps) required for general lighting and receptacles in a dwelling unit? 

A. NEC Article 210.3 specifies the rating requirements for branch circuits. For general lighting and receptacles 15 amps is the minimum size circuit permissible.

Monday August 26th 2024

Todays Daily Code Question. 

Q: What is the minimum size branch circuit (in amps) required for general lighting and receptacles in a dwelling unit? 

 

Friday's question..

Q: What is the minimum number of 20 amp branch circuits required for a kitchen in a dwelling unit?

A. NEC Article 210.11(C)(1) states that at least two 20 amp 120V small appliance receptacle branch circuits are required in the kitchen, pantry, breakfast room or similar area of a dwelling unit. 

Friday August 23rd 2024

Todays Daily Code Question. 

Q: What is the minimum number of 20 amp branch circuits required for a kitchen in a dwelling unit?

 

Yesterday's question..

Q: What are the specific requirements for outdoor outlets in a dwelling unit? 

A. NEC 210.52(E) At least one receptacle outlet must be installed at the front and the back of each dwelling unit. These outlets must be readily accessible from grade and must not be more than 6.5 feet above grade level. 
Balconies, decks or porches accessible from inside with an area of 20 sq feet (1.86 sq meters) must have at least one receptacle outlet. 
All outdoor outlets must be GFCI protected as per NEC 210.8(A)(3)  

Thursday August 22nd 2024

Todays Daily Code Question. 

Q: What are the specific requirements for outdoor outlets in a dwelling unit? 

 

Yesterday's question..

Q: What are tamper resistant outlets and where are they required? 

A. NEC 406.12. Tamper-resistant outlets are designed to prevent children from inserting foreign objects into an outlet and they are required in all areas of a dwelling unit, including; Bedrooms, Living rooms, Dining rooms, Hallways, Bathrooms, Kitchens, Outdoors.

Wednesday August 21st 2024

Todays Daily Code Question. 

Q: What are tamper resistant outlets and where are they required? 

Yesterday's question..

Q: What is the minimum size conductor required for a 20 amp branch circuit? 

 

A. NEC 210.19(A)(4): Specifies the minimum conductor sizes for branch circuits. 
For a 20-amp branch circuit, #12 AWG copper or #10 AWG aluminum is required. 

Tuesday August 20th 2024

Todays Daily Code Question. 

Q: What is the minimum size conductor required for a 20 amp branch circuit? 

 

Yesterday's question..

Q: According to the NEC, how far apart should receptacles be spaced along the wall line in a dwelling unit? 

 

A. Article 210.52. Receptacles should be installed such that no point measured horizontally along the floor line of any wall space is more than 1.8m (6 feet) from a receptacle outlet. 

Receptacle outlets must be installed in any wall that is 2 feet (600mm) or more in width. 

Monday August 19th 2024

Todays Daily Code Question. 

Q: According to the NEC, how far apart should receptacles be spaced along the wall line in a dwelling unit? 

 

Friday's question..

Q: What are the NEC regulations regarding the spacing of kitchen countertop receptacles?

 

A. Article 210.52 (C) states that countertop receptacle outlets must be placed so that no point along the wall line is more than 24 inches measured horizontally from a receptacle outlet. At least one receptacle outlet must be installed at each island or peninsula countertop with a long dimension of 24 inches and a short dimension of 12 inches or greater. The receptacles can be mounted below the countertop provided that they are no more than 12 inches below the countertop and the countertop does not extend more than 6 inches beyond its support base. 

Friday August 16th 2024

Todays Daily Code Question. 

Q: What are the NEC regulations regarding the spacing of kitchen countertop receptacles?

Yesterday's question..

Q. How does the NEC regulate the use of flexible cords and cables? 

A. Article 400 deals with flexible cords and cables. They are generally limited to specific uses such as for pendants, portable lamps, connection of portable appliances and temporary wiring during construction. 
Flexible cords cannot be used as a substitute for fixed wiring, run through walls, ceilings or floors and they can not be concealed. 

 

 

Thursday August 15th 2024

Todays Daily Code Question. 

Q: How does the NEC regulate the use of flexible cords and cables? 

Yesterday's question..

Q. What are the NEC's requirements for circuit breaker sizing?

A. (Article 240.4) Circuit Breakers must be sized according to circuit they are being used to protect and they must never be sized greater than the ampacity rating of the wiring being used.

Wednesday August 14th 2024

Todays Daily Code Question. 

Q: What are the NEC's requirements for circuit breaker sizing?

Yesterday's question..

Q. Where is a GFI required?

A. (Article 210.8) GFI's are required in locations where the risk of electrical shock is higher due to the presence of water or moisture.

The NEC mandates GFCI's in Bathrooms, Kitchens, Garages and Accessory Buildings, Outdoor Areas, Basements, Laundry Areas, Utility Rooms, Crawl Spaces, Swimming Pools, Spa's and Hot Tubs and Boathouses, 

Tuesday August 13th 2024

Todays Daily Code Question. 

Q: Where is a GFI required?

Yesterday's question..

Q. What is the difference between a GFCI and an AFCI?

A. A GFCI is a Ground Fault Circuit Interrupter is designed to protect individuals against electrical shock by shutting off the power when any portion of the current escapes to ground. 

An AFCI, Arc-Fault Circuit Interrupter is designed to protect against fire risk by recognizing the waveforms associated with Arc faults and shutting the power off when they occur.

Monday August 12th 2024

Todays Daily Code Question. 

Q: What is the difference between a GFCI and an AFCI?

Friday's question..

Q. What are branch circuits and what Article of Code deals with them?

A.  Branch circuits deliver power from an electrical panel to individual devices like outlets, lights, appliances or other electrical devices in a building.  Essentially a branch circuit is the wiring and associated devices like breakers, outlets and switches that carry power from the panel to the point of use. 

Article 210 of the NEC deals with branch circuits.

Friday August 9th 2024

Todays Daily Code Question. 

Q: What are branch circuits and what Article of Code deals with them?

Yesterday's question..

Q. What is Article 250 of the NEC

A. Article 250 of the NEC covers the requirements for grounding and bonding in electrical installations. Grounding and bonding are critically important safety measures for the protection of people and property from electrical shock and fire hazards.

Thursday August 8th 2024

Todays Daily Code Question. 

Q: What is Article 250 of the NEC

 

Yesterday's question..

Q. How is the NEC organized? 

A. The NEC is organized into 9 Chapters each of which focuses on a different aspect of electrical installation and safety requirements. The Chapters are further divided into articles which cover specific topics in detail.

Wednesday August 7th 2024

Todays Daily Code Question. 

Q: How is the NEC organized? 

Yesterday's question..

Q. How often is the NEC updated?

A. The NEC is updated every three years to reflect new technologies and improved safety standards

Tuesday August 6th 2024

Todays Daily Code Question. 

Q: How often is the NEC updated?

Yesterday's question..

Q. Who publishes the NEC?

A. The NEC is published by the National Fire Protection Association (NFPA)

Monday August 5th 2024

Todays Daily Code Question. 

Q: Who publishes the NEC?

Yesterday's question..

Q. What is the primary function of the National Electrical Code? 

A. The primary function of the NEC is to ensure the safe installation and use of electrical wiring and equipment by providing a set of standards and guidelines to be followed.

Friday August 2nd 2024

Todays Daily Code Question. 

Q: What is the primary function of the National Electrical Code? 

Yesterday's question.

Q. What is the National Electrical Code? 

A. The National Electrical Code (NEC) is a set of Safety Standards and Guidelines for Electrical wiring and equipment in the United States. 

Thursday August 1st 2024

Q: What is the National Electrical Code?

The answer will be attached to tomorrows Daily Code Question

bottom of page